Amp to kW single phase

Convert current to real power on a single-phase AC supply and see how the power factor shifts current away from voltage.

Inputs

A
V
PF
Real power
0kW

Voltage, current and instantaneous power

How amp to kW single phase calculator works

The amp to kW single phase calculator converts current into real power in kilowatts (kW) on a single-phase alternating current (AC) supply with 3 inputs: current, voltage and power factor. The calculator returns real power, apparent power in kilovolt-amperes (kVA), reactive power in kilovolt-amperes reactive (kVAR) and watts.

16 A at 230 V and PF 0.9 gives 3.312 kW, 3.68 kVA and 1.6 kVAR. The waveform shades the instantaneous power above and below zero.

Amp to kW single phase formula

The amp to kW single phase formula is P(kW) = I(A) × V(V) × PF / 1,000. There are 3 single-phase power formulas: real power, apparent power and reactive power.

Real power

P(kW) = I × V × PF / 1000

16 A × 230 V × 0.9 / 1,000 = 3.312 kW

Apparent power

S(kVA) = I × V / 1000

16 A × 230 V / 1,000 = 3.68 kVA

Reactive power

Q(kVAR) = √(S² − P²)

√(3.68² − 3.312²) = 1.6 kVAR

Power factor (PF) values fall into 4 groups: 1 for heaters, kettles and incandescent lamps, 0.95–0.99 for electronics with power factor correction, 0.8–0.9 for loaded induction motors and 0.5–0.7 for lightly loaded motors.

Amp to kW single phase conversion chart

The amp to kW single phase conversion chart lists 13 currents from 1 A to 63 A at 120 V, 230 V and 240 V, plus 230 V columns at power factor 0.9 and 0.8.

Amps120 VPF 1230 VPF 1240 VPF 1230 VPF 0.9230 VPF 0.8
1 A0.120.230.240.210.18
5 A0.61.151.21.040.92
10 A1.22.32.42.071.84
13 A1.562.993.122.692.39
15 A1.83.453.63.112.76
16 A1.923.683.843.312.94
20 A2.44.64.84.143.68
25 A35.7565.184.6
30 A3.66.97.26.215.52
32 A3.847.367.686.625.89
40 A4.89.29.68.287.36
50 A611.51210.359.2
63 A7.5614.4915.1213.0411.59

A 63 A single-phase supply delivers 14.49 kW at 230 V and 15.12 kW at 240 V, at a power factor of 1.

Amp to kW single phase Excel formula

The amp to kW single phase Excel formula is =A2*B2*C2/1000 with amps in A2, volts in B2 and power factor in C2.

D2fx=ROUND(A2*B2*C2/1000,2)
ABCDE
1AmpsVoltsPFkWFormula in D
2162300.93.31=ROUND(A2*B2*C2/1000,2)
33224017.68=ROUND(A3*B3*C3/1000,2)
4151200.81.44=ROUND(A4*B4*C4/1000,2)

Add =A2*B2/1000 in column E for kVA and =SQRT(E2^2-D2^2) in column F for kVAR.

Amp to kW single phase equation

The amp to kW single phase equation is P = Vrms × Irms × cos φ, where φ is the angle between the voltage and current waves.

P
Real power in kilowatts (kW)
I
Current in amperes (A), RMS
V
Voltage in volts (V), RMS
PF
Power factor, cos φ, from 0 to 1

Root mean square (RMS) values are the values a multimeter or a clamp meter shows. A 230 V RMS supply peaks at 325.3 V (230 × √2).

Amp to kW single phase FAQ

How many kW is 16 amps single phase?

16 amps single phase is 3.68 kW at 230 V, 3.84 kW at 240 V and 1.92 kW at 120 V, at a power factor of 1.

How many kW is 32 amps single phase?

32 amps single phase is 7.36 kW at 230 V and 7.68 kW at 240 V, at a power factor of 1.

What power factor should I use for single phase?

Use 1 for heaters and kettles, 0.95 for electronics with power factor correction and 0.75–0.85 for single-phase motors. The nameplate power factor gives the most accurate result.

How many kW can a 100 amp single phase supply carry?

A 100 amp single phase supply carries 23 kW at 230 V and 24 kW at 240 V, at a power factor of 1.