Amps to kW 415V
Convert current to kW on a 415 V three-phase supply and see how the power splits across L1, L2 and L3.
Inputs
Power carried by each phase
How amps to kW 415V calculator works
The amps to kW 415V calculator converts line current into kilowatts (kW) on a 415 V three-phase supply with 3 inputs: current, power factor and phase. The calculator splits the total kW across L1, L2 and L3 for a balanced load.
P = √3 × I × 415 × PF / 100063 A at 415 V and PF 0.85 gives 38.49 kW, or 12.83 kW on each phase. The column chart shows each phase and the stacked total.
Amps to kW 415V formula
The amps to kW 415V formula is P(kW) = √3 × I × 415 × PF / 1,000. There are 3 formulas at 415 V: three-phase power, power per phase and single-phase power at 240 V.
Three phase 415 V
P = √3 × I × 415 × PF / 10001.732 × 63 A × 415 V × 0.85 / 1,000 = 38.49 kW
Per phase
Pphase = P / 338.49 kW / 3 = 12.83 kW
Single phase 240 V
P = I × 240 × PF / 100032 A × 240 V / 1,000 = 7.68 kW
415 V line to line gives 239.6 V line to neutral (415 ÷ √3). 415/240 V systems serve industry in India, Malaysia, Singapore, Hong Kong and older Australian and UK installations.
Amps to kW 415V conversion chart
The amps to kW 415V conversion chart lists 13 line currents from 10 A to 400 A at 415 V three phase at power factor 1, 0.9, 0.85 and 0.8, plus kW per phase at PF 1.
| Amps | 415 VPF 1 | 415 VPF 0.9 | 415 VPF 0.85 | 415 VPF 0.8 | Per phasePF 1 |
|---|---|---|---|---|---|
| 10 A | 7.19 | 6.47 | 6.11 | 5.75 | 2.4 |
| 16 A | 11.5 | 10.35 | 9.78 | 9.2 | 3.83 |
| 20 A | 14.38 | 12.94 | 12.22 | 11.5 | 4.79 |
| 32 A | 23 | 20.7 | 19.55 | 18.4 | 7.67 |
| 40 A | 28.75 | 25.88 | 24.44 | 23 | 9.58 |
| 63 A | 45.28 | 40.76 | 38.49 | 36.23 | 15.09 |
| 80 A | 57.5 | 51.75 | 48.88 | 46 | 19.17 |
| 100 A | 71.88 | 64.69 | 61.1 | 57.5 | 23.96 |
| 125 A | 89.85 | 80.87 | 76.37 | 71.88 | 29.95 |
| 160 A | 115.01 | 103.51 | 97.76 | 92.01 | 38.34 |
| 200 A | 143.76 | 129.38 | 122.2 | 115.01 | 47.92 |
| 250 A | 179.7 | 161.73 | 152.75 | 143.76 | 59.9 |
| 400 A | 287.52 | 258.77 | 244.39 | 230.02 | 95.84 |
A 400 A, 415 V supply delivers 287.52 kW at PF 1.
Amps to kW 415V Excel formula
The amps to kW 415V Excel formula is =SQRT(3)*A2*415*B2/1000 with line amps in A2 and power factor in B2.
| A | B | C | D | E | |
|---|---|---|---|---|---|
| 1 | Amps | Volts | PF | kW | Formula in D |
| 2 | 63 | 415 | 0.85 | 38.49 | =ROUND(SQRT(3)*A2*B2*C2/1000,2) |
| 3 | 100 | 415 | 0.9 | 64.69 | =ROUND(SQRT(3)*A3*B3*C3/1000,2) |
| 4 | 200 | 415 | 1 | 143.76 | =ROUND(SQRT(3)*A4*B4*C4/1000,2) |
Add =D2/3 in column E for kW per phase.
Amps to kW 415V equation
The amps to kW 415V equation is P = √3 × I × 415 × PF / 1,000, where 415 is the line-to-line voltage.
- P
- Total real power in kW
- I
- Line current in amperes (A)
- 415
- Line-to-line voltage (V)
- PF
- Power factor
Each amp at 415 V three phase and PF 1 adds 0.719 kW.
Amps to kW 415V FAQ
How many kW is 100 amps at 415V?
100 amps at 415V three phase is 71.88 kW at a power factor of 1 and 61.1 kW at 0.85.
How many kW is 63 amps at 415V?
63 amps at 415V three phase is 45.28 kW at a power factor of 1.
How many amps is 50 kW at 415V?
50 kW at 415V three phase is 69.56 A per line at a power factor of 1 and 81.84 A at 0.85.
What is the single phase voltage of a 415V supply?
The single phase voltage of a 415V supply is 239.6 V (415 ÷ √3), usually called 240 V.