Amps to kW 480V

Convert current to kW on a 480 V supply and compare how much more power the same current carries than at lower voltages.

Inputs

Current type
A
V
Voltage measured three phase
PF
Real power
0kW

Same current at other voltages

How amps to kW 480V calculator works

The amps to kW 480V calculator converts line current into kilowatts (kW) on a 480 V supply with 3 inputs: current, power factor and phase. The column chart compares the same current at 9 voltages from 120 V to 600 V.

200 A at 480 V three phase and PF 0.9 gives 149.65 kW. The same 200 A at 208 V gives 64.85 kW.

Amps to kW 480V formula

The amps to kW 480V formula is P(kW) = √3 × I × 480 × PF / 1,000. There are 3 formulas on a 480 V system: three phase, 480 V single phase and 277 V single phase.

Three phase 480 V

P = √3 × I × 480 × PF / 1000

1.732 × 200 A × 480 V × 0.9 / 1,000 = 149.65 kW

Single phase 480 V

P = I × 480 × PF / 1000

30 A × 480 V / 1,000 = 14.4 kW

Single phase 277 V

P = I × 277 × PF / 1000

20 A × 277 V / 1,000 = 5.54 kW

480Y/277 V is the standard commercial and industrial supply in the United States and Canada: 480 V feeds motors and chillers, and 277 V feeds lighting. National Electrical Manufacturers Association (NEMA) motors list 460 V on the nameplate for 480 V systems.

Amps to kW 480V conversion chart

The amps to kW 480V conversion chart lists 13 line currents from 10 A to 1,000 A at 480 V: three phase at power factor 1, 0.9 and 0.85, single phase at 480 V and single phase at 277 V.

Amps480 V 3φPF 1480 V 3φPF 0.9480 V 3φPF 0.85480 V 1φPF 1277 V 1φPF 1
10 A8.317.487.074.82.77
20 A16.6314.9614.139.65.54
30 A24.9422.4521.214.48.31
50 A41.5737.4135.332413.85
60 A49.8844.8942.428.816.62
100 A83.1474.8270.674827.7
150 A124.71112.241067241.55
200 A166.28149.65141.349655.4
225 A187.06168.3615910862.33
400 A332.55299.3282.67192110.8
600 A498.83448.95424.01288166.2
800 A665.11598.6565.34384221.6
1,000 A831.38748.25706.68480277

A 1,000 A, 480 V switchboard carries 831 kW at PF 1.

Amps to kW 480V Excel formula

The amps to kW 480V Excel formula is =SQRT(3)*A2*480*B2/1000 with line amps in A2 and power factor in B2.

D2fx=ROUND(SQRT(3)*A2*B2*C2/1000,2)
ABCDE
1AmpsVoltsPFkWFormula in D
22004800.9149.65=ROUND(SQRT(3)*A2*B2*C2/1000,2)
3100480183.14=ROUND(SQRT(3)*A3*B3*C3/1000,2)
42027715.54=ROUND(A4*B4*C4/1000,2)

Row 4 is a 277 V lighting circuit.

Amps to kW 480V equation

The amps to kW 480V equation is P = √3 × I × 480 × PF / 1,000 for a three-phase supply.

P
Total real power in kW
I
Line current in amperes (A)
480
Line-to-line voltage (V)
PF
Power factor

Each amp at 480 V three phase and PF 1 adds 0.831 kW, 2.31 times the kW per amp at 208 V.

Amps to kW 480V FAQ

How many kW is 100 amps at 480V?

100 amps at 480V three phase is 83.14 kW at a power factor of 1 and 74.82 kW at 0.9.

How many kW is 200 amps at 480V?

200 amps at 480V three phase is 166.28 kW at a power factor of 1 and 149.65 kW at 0.9.

How many amps is 100 kW at 480V?

100 kW at 480V three phase is 120.28 A per line at a power factor of 1 and 133.65 A at 0.9.

What is 277V on a 480V system?

277V is the line-to-neutral voltage of a 480V three-phase system (480 ÷ √3), used for commercial lighting.